          General specifications Signal type Analog output Supply Connection Power Rail or terminals 7+, 8- Rated voltage 20 ... 35 V DC Ripple within the supply tolerance Rated current current output: ≤ 50 mA ; voltage output: ≤ 20 mA

          KFD2-CD-EX1.32KFD2-CD-EX1.32
          1-channel
          Output EEx ia IIC
          24 V DC nominal supply voltage
          Device installation permissible in
          zone 2
          Conversion of current to voltage or 
          voltage to current
          Elevation/Suppression of the "life
          zero"
          Accuracy 0.1 %
          EMC acc. to NAMUR NE 21

           
          Signal type Analog output
          Supply
          Connection Power Rail or terminals 7+, 8-
          Rated voltage 20 ... 35 V DC
          Ripple within the supply tolerance
          Rated current current output: ≤ 50 mA ; voltage output: ≤ 20 mA
          Power loss 1.2 W
          Input
          Connection terminals 9+, 10-, 11+
          Voltage drop optional current input: approx. 4 V at 20 mA
          Input current ≤ 100 µA up to 50 °C (122 °F) at 10 V
          Limit optional current input: Input current: approx. ≤40 mA
          optional voltage input: input voltage: 12 V DC
          Transmission range optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V
          Output
          Connection terminals 1+, 2-
          Current optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA
          Load optional current output: max. 850 Ω
          optional voltage output: output resistance max. 3 Ω
          Voltage optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V
          Transfer characteristics
          Rise time < 10 ms
          Directive conformity
          Electromagnetic compatibility  
            Directive 2004/108/EC EN 61326-1:2006
          Conformity
          Insulation coordination EN 50178
          Electrical isolation EN 50178
          Protection degree IEC 60529
          Ambient conditions
          Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
          Mechanical specifications
          Protection degree IP20
          Mass approx. 100 g
          Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) , housing type B1
          Data for application in connection with Ex-areas
          EC-Type Examination Certificate BAS 02 ATEX 7203 , for additional certificates see www.pepperl-fuchs.com
            Group, category, type of protection II (1)GD, I (M1), [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
          Statement of conformity TÜV 99 ATEX 1499 X , observe statement of conformity
            Group, category, type of protection, temperature class II 3G Ex nA II T4
          Directive conformity  
            Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2012, EN 60079-15:2005
          International approvals
          FM approval  
            Control drawing 116-0129
          UL approval  
            Control drawing 116-0173 (cULus)
          CSA approval  
            Control drawing 116-0132
          IECEx approval IECEx BAS 05.0041
            Approved for [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I

          1、安全柵應(yīng)安裝在非危險(xiǎn)場(chǎng)所。
          2、安全柵通往現(xiàn)場(chǎng)(危險(xiǎn)場(chǎng)所)的軟銅導(dǎo)線截面積必須大于0.5mm²。
          3、連接導(dǎo)線的絕緣強(qiáng)度大于500V。
          4、安全柵本安端(有藍(lán)色標(biāo)記)和非本安端電路配線,不得接錯(cuò)和混淆。本安導(dǎo)線宜選用藍(lán)色作為本安標(biāo)記。本安導(dǎo)線和非本安導(dǎo)線在匯線槽中應(yīng)分開鋪設(shè),采用各自保護(hù)套管。安全
          柵的本安側(cè),不允許混淆有其它電源,包括其它本安電路的電源。
          5、安全柵與一次儀表組成本安安全防爆系統(tǒng)時(shí),必須經(jīng)國(guó)家指定的防爆檢驗(yàn)機(jī)構(gòu)檢驗(yàn)認(rèn)可。PH系列安全柵安全柵由國(guó)家防爆電氣監(jiān)督檢驗(yàn)中心,給出的Co,Lo分布參數(shù)是相對(duì)與ⅡC級(jí)(氫氣級(jí))的最大允許值對(duì)于ⅡB級(jí)環(huán)境可把該參數(shù)乘以3,對(duì)于ⅡA級(jí)環(huán)境可把該參數(shù)乘以8。傳輸線選用不同規(guī)格的電纜時(shí),其本身的電纜參數(shù)應(yīng)予高度重視,不得超過(guò)規(guī)定值。
          6、對(duì)安全柵進(jìn)行單獨(dú)通電調(diào)試時(shí),必須注意安全柵的型號(hào)、電源極性、電壓等級(jí)及安全柵外殼接線端上的標(biāo)號(hào)。
          7、嚴(yán)禁用兆歐表測(cè)試隔離安全柵端子之間的絕緣性。若要檢查系統(tǒng)線路絕緣性時(shí),應(yīng)先斷開全部安全柵接線,否則會(huì)引起內(nèi)部器件損壞。
          General specifications
          Signal type Analog output
          Supply
          Connection Power Rail or terminals 7+, 8-
          Rated voltage 20 ... 35 V DC
          Ripple within the supply tolerance
          Rated current current output: ≤ 50 mA ; voltage output: ≤ 20 mA
          Power loss 1.2 W
          Input
          Connection terminals 9+, 10-, 11+
          Voltage drop optional current input: approx. 4 V at 20 mA
          Input current ≤ 100 µA up to 50 °C (122 °F) at 10 V
          Limit optional current input: Input current: approx. ≤40 mA
          optional voltage input: input voltage: 12 V DC
          Transmission range optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V
          Output
          Connection terminals 1+, 2-
          Current optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA
          Load optional current output: max. 850 Ω
          optional voltage output: output resistance max. 3 Ω
          Voltage optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V
          Transfer characteristics
          Rise time < 10 ms
          Directive conformity
          Electromagnetic compatibility  
            Directive 2004/108/EC EN 61326-1:2006
          Conformity
          Insulation coordination EN 50178
          Electrical isolation EN 50178
          Protection degree IEC 60529
          Ambient conditions
          Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
          Mechanical specifications
          Protection degree IP20
          Mass approx. 100 g
          Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) , housing type B1
          Data for application in connection with Ex-areas
          EC-Type Examination Certificate BAS 02 ATEX 7203 , for additional certificates see www.pepperl-fuchs.com
            Group, category, type of protection II (1)GD, I (M1), [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
          Statement of conformity TÜV 99 ATEX 1499 X , observe statement of conformity
            Group, category, type of protection, temperature class II 3G Ex nA II T4
          Directive conformity  
            Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2012, EN 60079-15:2005
          International approvals
          FM approval  
            Control drawing 116-0129
          UL approval  
            Control drawing 116-0173 (cULus)
          CSA approval  
            Control drawing 116-0132
          IECEx approval IECEx BAS 05.0041
            Approved for [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I